XHHW-2 ALUMINUM CONDUCTOR
APPLICATION:
KINGWIRE 1000/600 Volt Type XHHW-2 is intended for use as general purpose wiring for up to 1000 volt rated services in air conduit or other recognized raceways for services, feeders and branch circuit wiring as specified in the National Electrical Code at a maximum conductor temperature of 90 °C in wet or dry locations.
PRODUCT FEATURES:
Compact stranded 8000 Series aluminum alloy conductor. Insulation is an abrasion, moisture, heat and sunlight resistant black cross-linked polyethylene.
Cable can be installed without pulling lubricant.
CT Rated Standard For Sizes 1/0 AWG and larger.
STANDARDS:
UL Standard 44 and Federal Specification JC-30B NEC, ASTM B-800, B-801
Compliant to RoHS, Directive 2002/95/EC, ICEA S-95-658, NEMA WC 70
COLORS:
Sizes 6 to 2 gauge are stocked in Black, White, Red, Blue and Green.
Sizes 1 to 750MCM stocked in all the above colors plus Brown, Yellow, Orange, Gray, Green and Purple.
KINGWIRE XHHW-2 |
|||||
Conductor (AWG or MCM) |
Stranding |
Insulation Thickness (mls) |
Outside Diameter (in) |
Weight per 1000 ft. (lbs) |
Ampacity (AMPS) * 90° C |
6 |
7/w |
45 |
.260 |
39 |
60 |
4 |
7/w |
45 |
.305 |
57 |
75 |
2 |
7/w |
45 |
.360 |
84 |
100 |
1 |
19/w |
55 |
.415 |
108 |
115 |
1/0 |
19/w |
55 |
.450 |
132 |
135 |
2/0 |
19/w |
55 |
.490 |
161 |
150 |
3/0 |
19/w |
55 |
.540 |
198 |
175 |
4/0 |
19/w |
55 |
.590 |
244 |
205 |
250 |
37/w |
65 |
.655 |
292 |
230 |
300 |
37/w |
65 |
.705 |
344 |
255 |
350 |
37/w |
65 |
.750 |
396 |
280 |
400 |
37/w |
65 |
.795 |
448 |
305 |
500 |
37/w |
65 |
.870 |
550 |
350 |
600 |
61/w |
80 |
.980 |
671 |
385 |
700 |
61/w |
80 |
1.040 |
774 |
420 |
750 |
61/w |
80 |
1.075 |
824 |
435 |
900 |
61/w |
80 |
1.161 |
.979 |
480 |
1000 |
61/w |
80 |
1.230 |
1079 |
500 |
1. Data are approximate and subject to normal manufacturing tolerances.
2. Standard lengths are subject to normal manufacturing tolerance of +/- 10%
3. Two, Three or four conductors can be paralleled on a reel.
4. 90°C- XHHW-2 wet or dry locations.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.