CONSTRUCTION PARAMETERS:

INSULATION: Flame retardant Cross-Linked Polyethylene (XLPE)

INSULATION COLOR: Black and Red

 

PHYSICAL PROPERTIES:

TEMPERATURE RANGE: -40°C to 90°C Dry, 90°C Wet. Rated for direct burial, moisture resistant, meets cold bend & cold impact test at -40°C

 

ELECTRICAL PROPERTIES

VOLTAGE RATING: 2,000 V for interconnection wiring of grounded and ungrounded photovoltaic power systems as described in Section 690.31 (A) and other applicable parts of the National Electrical Code (NEC), NFPA 70

 

STANDARDS:

ULlogo1 

UL 44 Type RHH/RHW-2, 2000V, UV/Sunlight Resistant
UL 854 Type USE-2
UL 4703 Type PV
ASTM B-800 , B-801
Flame Test: UL 1581 VW-1
IEEE383 for sizes 1/0 AWG and larger
ROHS, EPA 40 CFR, Part 26, Subpart C, heavy metals per Table 1, TLCP method
ASTM B836 COMPACT ROUNDED STRANDED ALUMINUM CONDUCTORS

 

 

KINGWIRE AL 2KV TYPE PV

Conductor Size
(AWG ,Kcmil)

Conductor
Stranding
(#/AWG)

Nominal
Conductor
Diameter
(in)

Min. Ave. Insulation
Thickness
(in)

Nominal
Overall
Diameter
(in)

Aluminum
Weight
(lbs/1000ft)

Net Weight
(lbs./1000ft)

350

26/.1280

0.607

0.120

0.847

329

479

400

37/.1110

0.659

0.120

0.899

377

548

500

37/.1235

0.736

0.120

0.976

471

685

600

61/.1030

0.813

0.135

1.083

565

822

750

61/.1140

0.908

0.135

1.178

706

1027

Notes:
All dimensions and weights are subject to industry standards and tolerance unless otherwise noted.