APPLICATION

KINGWIRE Service Entrance Cable Style R (SER) is used to convey power from the service drop to the meter base and from the meter base to the distribution panel board. It can be used for both above ground service entrance and interior wiring applications at temperatures not to exceed 90°C. The voltage rating is 600V.

PRODUCT FEATURES

  • KINGWIRE Type SE cable is constructed with AA-8000 series aluminum alloy, compact stranded conductors.
  • Cross-linked polyethylene insulation rated for a maximum operation temperature of 90°C in wet and dry locations.
  • Eco friendly sunlight resistant, flame retardant and heavy metal free Polyvinyl Chloride (PVC) Jacket.
  • Insulation and Jacket materials are in compliance with RoHS, Directive 2002/95/EC.
  • Sequential foot markings for easier inventory control management.

STANDARDS

ULlogo1 

UL Standard 44 for type XHHW-2 conductors, (UL) Standard 854, Federal Specification JC-30B NEC

 

KINGWIRE Service Entrance Cable Style R (SER) - 2 Conductor with Ground SER

Size AWG &

Construction

Stranding

Nominal

Diameter

(in)

Weight per

1000 ft. (lbs)

Ampacity (AMPS) *

Phase
Conductors

Equipment Ground

Conductor

90˚ C

Dwelling

6-6-6

7

-

.650

150

60

-

4-4-6

7

-

.681

196

75

-

4-4-4

7

-

.682

196

75

-

Notes: Data are approximate and subject to normal manufacturing tolerances.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.

KINGWIRE Service Entrance Cable Style R (SER) - 3 Conductor with Ground SER

Size AWG &

Construction

Stranding

Nominal

Diameter

(in)

Weight per

1000 ft. (lbs)

Ampacity (AMPS) *

Phase
Conductors

Equipment Ground

Conductor

90˚ C

Dwelling

8-8-8-8

Solid

Solid

.588

128

45

-

6-6-6-6

7

7

.684

180

60

-

4-4-4-6

7

7

.754

240

75

-

2-2-2-4

7

7

.893

344

100

100

1-1-1-3

19

7

1.003

432

115

110

1/0-1/0-1/0-2

19

7

1.097

521

135

125

2/0-2/0-2/0-1

19

19

1.197

633

150

150

3/0-3/0-3/0-1/0

19

19

1.314

771

175

175

4/0-4/0-4/0-2/0

19

19

1.443

942

205

200

250-250-250-3/0

37

19

1.601

1106

230

225

300-300-300-4/0

37

19

1.719

1360

255

230

 

KINGWIRE Service Entrance Cable Style R (SER) - 4 Conductor with Ground SER

Size AWG &

Construction

Stranding

Nominal

Diameter

(in)

Weight per

1000 ft. (lbs)

Ampacity (AMPS) *

Phase
Conductors

Equipment Ground

Conductor

90˚ C

Dwelling

2-2-2-2-4

7

7

1.004

450

100

100

2/0-2/0-2/0-2/0-1

19

19

1.346

824

150

150

4/0-4/0-4/0-4/0-2/0

19

19

1.621

1226

205

200

250-250-250-250-3/0

37

19

1.950

1454

230

225

Notes: Data are approximate and subject to normal manufacturing tolerances.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.