600 VOLT
SECONDARY UD - QUADRUPLEX

600 VOLT SECONDARY UD - QUADRUPLEX

APPLICATION

Directly buried or installed in ducts for 600 volt secondary distribution.

PRODUCT FEATURES

Concentric stranded or compressed 1350-H19 aluminum conductor, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral, triple yellow striped or solid yellow. Black neutrals may be specified if desired.

STANDARDS

ULlogo1

UL Standard 854 for Type USE-2
ASTM B-230, B-231 and ICEA S-105-692
Federal Specification JC-30B NEC

 

KINGWIRE Quadruplex Conductor 600 Volt Secondary Type URD Cable - Aluminum Conductor

Code Word

Phase Conductors

Neutral Conductor

Single
Phase
Conductor
(in)

Outside
Diameter
(in)

Weight
per 1000 ft
(lbs)

Ampacity

Size
AWG

Strand

Insulation Thickness
(MLS)

Size
AWG

Strand

Insulation Thickness
(MLS)

Direct Burial

In Duct

Tulsa

4

7/w

60

4

7/w

60

.345

.833

258

119

85

Dyke

2

7/w

60

4

7/w

60

.403

.938

346

153

115

Wittenberg

2

7/w

60

2

7/w

60

.403

.973

375

153

115

Notre Dame

1/0

19/w

80

2

7/w

60

.522

1.188

541

198

150

Purdue

1/0

19/w

80

1/0

19/w

80

.522

1.260

596

198

150

Syracuse

2/0

19/w

80

1

19/w

80

.566

1.316

664

225

170

Wake Forest

4/0

19/w

80

2/0

19/w

80

.672

1.560

979

290

225

Rust

250

37/w

95

3/0

19/w

80

.748

1.725

1,176

319

240

Slippery Rock

350

37/w

95

4/0

19/w

80

.851

1.945

1,544

385

305

Wofford

500

37/w

95

350

37/w

95

.851

2.348

2,174

467

420

Westminster

750

61/w

110

350

37/w

95

.979

2.722

2,816

615

492

Ampacity: 90°C conductor temperature, 20°C ambient, RHO 90, 100% load factor for three conductor triplex with neutral carrying only unbalanced load.
All Yellow Extruded Stripe, cable is XLP insulation.
* To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
The above data are approximate and subject to normal manufacturing tolerances.